The robust rectifier which is also suitable for aggressive ambient conditions.

General

The basic rectifier design of the regulated transformer rectifier series is characterized by a motor-adjustable regulating transformer drive and a high-current transformer with downstream silicon diode set in 6-pulse circuit.

Individual devices from:

  • UDC = 0 - 1.500 V
  • IDC = 100 - 20.000 A
Technical Data
  • Mains: 3 x 400V/50Hz (worldwide network adaptation possible)
  • Regulating: via binary more/less signal
  • Setting range: stepless electronic 0...100%
  • Signals: current, voltage, status, fault (individual fault messages optional)
  • Control: interface via 16-pin Harting connector
  • Ripple: approx. 5% at regulated full-DC-output voltage (optional with smoothing)
  • Rectifier connection: 6-pulse rectifier-connection (optional 12-pulse)
  • Operating mode: 100% duty cycle
  • Ambient temperature: +35°C (higher temperatures conditions possible)
  • Cooling: natural convection or oil/water cooling
  • Detection: phase position; phase sequence; phase failure; mains undervoltage; short-circuit detection; temperature
  • Degreee of protection: IP54
Options
  • Field-bus interface (Profibus; Profinet; Modbus; RS-485 etc.)
  • Additional motor controller: setpoint 0-10V, 4-20mA, 0-20mA
  • Mechanical change of output polarity (bipolar operation)
  • Transformer taps
  • Smoothing devices (L and LC smoothing up to 1% possible)
  • Ah-counter-integration
  • Remote control (optional with timers or SPS control)
  • Special designs according to customer requirements possible without any problems
Oil cools and protects
  • Intensive cooling of components
  • Protection against corrosion
  • Outdoor installation also possible
  • No noise pollution
  • Low maintenance and reliable